Most commercial kitchen exhausts in WA cost more than they need to, and the reason is rarely the equipment. It is a handful of decisions made on the first layout, before anyone opens the Standard. The seven below come from kitchen fit-outs I have designed in Perth.
The first layout most kitchens get is a canopy, a long grease duct across the ceiling to wherever the roof looks clear, a fan, a stack. It usually complies. It is also usually more expensive than it needs to be, and it tends to carry three assumptions that the Standards do not support. Here is what to change, and why.
The numbers are a worked example for a typical small production kitchen: four electric fryers under a wall canopy, two gas ovens, a dishwasher and an open-plan room of about 1200 m³. They illustrate the method; they are not any one job, and not a quotation. Clauses are quoted from AS 1668.2-2012 with Amendments 1 and 2 (the edition NCC 2022 calls up) and AS/NZS 5601.1:2022; check the edition your building surveyor uses.
- Put the fan above the hood
- Size the hood to the line, not the old canopy
- Treat the roof outlets as one group
- Check whether a 3 m stack is required
- Gas ovens change the air, not just the gas
- Make-up air is the other half
- Check every number before it is priced
DECISION 01Put the fan above the hood
Horizontal grease duct is the most expensive metre in a kitchen exhaust. It has to be welded or grease-tight, carry an access door at every bend and roughly every 3 m, hang from the roof structure, fall back towards the hood so grease drains, and be cleaned for the life of the kitchen. A vertical riser straight into a roof fan above the hood needs almost none of that: grease runs back to the hood gutter, and the cleaner reaches the whole riser from two doors.
Same hood, same airflow. The difference is where the fan sits.
| Worked example, grease system 1300 L/s | Routed | Fan above the hood |
|---|---|---|
| Grease duct length | about 20 m | about 2.5 m |
| Bends / access doors | 4 / 10 | 0 / 2 |
| Duct hangers in the ceiling void | about 15 | none, clamped at the roof |
| Fan duty (total pressure) | 500 Pa, 1.5 kW | 400 Pa, 1.1 kW |
| Installed cost difference (budget rates) | about A$15,000 to 20,000 less, plus less duct to clean every year | |
The catch is the roof: purlins, the neighbour's condensers and the fresh air intake decide whether a fan can sit there. Allow two 45° offsets in the riser to clear a purlin and the position almost always works. Check it on the roof, with the structure drawings, before anyone draws a duct route.
DECISION 02Size the hood to the line, not to the old canopy
AS 1668.2-2012 Table 3.1 sets the minimum exhaust for a wall canopy as Q = K × P × H, where P is the exposed perimeter of the hood and H is the height of its lower edge above the cooking surface. The airflow follows the hood, not what sits under it. A hood that is longer than the appliance line pulls more air for as long as the kitchen runs, and so does the make-up air that has to replace it.
Height matters just as much. Appendix E4 requires the lower edge to be at least 2 m above the floor and no more than 1.2 m above the cooking appliance. A canopy hung at 2.5 m for tall combi ovens has to come down to between 2000 and 2115 mm over fryers with a 915 mm pan. "The canopy is already there, just connect it" rarely survives that check. Cutting an old canopy down is possible, but it means re-welding, new filters and a fabricator's declaration, so price it against a new hood rather than assume it saves money.
DECISION 03Treat the roof outlets as one group, and move the intake
Kitchen exhaust is Type B effluent. Above 1000 L/s it is classed as objectionable (Table 3.3), and the Note to that table says outlets within a single 6 m radius count as one discharge for the flow rate. In the worked example the grease fan, the dishwasher fan and both oven vents sit within a few metres of a common centre, so the group is 1800 L/s and every outlet in it, even the small oven vents, has to meet Clause 3.10.3:
- Vertical discharge at 5 m/s or more. Measured at the outlet or terminal, not in the duct. 1300 L/s through a 400 × 400 riser is 8.1 m/s, but a roof fan with an outlet larger than 1.3 / 5 = 0.26 m² would fail. Small oven vents often run at about 3 m/s, so they get open reducing nozzles sized for about 6 m/s, which still passes if the oven fan delivers 10 % less than its data sheet.
- At least 6 m from any property boundary, street boundary, outdoor air intake or natural ventilation opening.
The instinct is to spread the outlets apart to avoid the grouping. It does not help: the grease fan alone is already over 1000 L/s, and spreading them adds duct and roof penetrations. Keep the outlets together and move the intake instead. An existing roof intake inside the 6 m of the new group means the kitchen, and the ovens' burners, breathe their own exhaust. On a recent job that is exactly where the old intake sat. It came out, and the new make-up air intake went to the far corner of the roof, clear of the 6 m.
Planning a café, bakery or restaurant fit-out in WA? Send the equipment list and floor plan. I will tell you early where the fans can go and what the roof needs.
Send your equipment listDECISION 04Check whether a 3 m stack is really required
"The exhaust has to go 3 m above the roof" is the most repeated rule on kitchen jobs. In AS 1668.2-2012 it sits in Clause 3.10.3(b), and that paragraph opens with "for a Type A effluent". Kitchen exhaust is Type B. What Type B needs is the 5 m/s and the 6 m of Decision 03, and Note 2 to Clause 3.10.2 recommends at least 2 m above a roof that people regularly walk on.
The 3 m for kitchens comes from some council food business guidelines, written on older editions of the Standard (Cockburn and Wanneroo, for example). Others simply refer to AS 1668.2 and set no height. And a 3 m figure in a council's health local law can turn out to cover a different type of premises altogether. Where no height applies, removing the stacks takes out sheet metal, stay wires, a support frame, a wind check on the roof and some fan pressure.
DECISION 05Gas ovens change the air, not just the gas
Most kitchen exhaust designs treat gas as the gasfitter's problem. The pipework and flues are, but the air the burners need is a ventilation design question, and AS/NZS 5601.1:2022 has specific rules for it.
A gas oven that takes combustion air from the room and sends its products up a flue is an open flued appliance (Cl 1.3.2.10). An open-plan kitchen is a room, not an enclosure (Cl 1.3.29). For a building approved after WA adopted the 2013 edition, Clause 6.4.6.3.1 asks for G = gas input / room volume:
| Step | Worked example |
|---|---|
| Open flued gas input T | 300 + 300 = 600 MJ/h |
| Room volume V | about 1200 m³ |
| G = T / V, limit 0.4 MJ/h per m³ for open flued appliances | 0.50, additional ventilation required |
| Natural pathway: opening direct to outside, 450 mm² per MJ/h (Table 6.4.6.2) | 0.270 m² effective free area |
| Mechanical pathway: 0.3 L/s per MJ/h for forced draught burners (Table 6.4.9) | 180 L/s, delivered at low level |
Three things catch people here. The 3 MJ/h per m³ figure that often gets quoted is the limit for flueless appliances, not flued ovens; used by mistake, it says no ventilation is needed. The 0.270 m² is effective free area after the louvre blades and insect mesh, so the louvre face is about twice that. And if the make-up air fan is the pathway, Table 6.4.9 calls for the air at low level, at or below the burners, which ceiling diffusers alone do not give; Clause 6.4.10 then requires an interlock that senses real air movement and shuts the gas if the supply fails.
A good report shows both pathways and says which it recommends and why. In a food premises the mechanical one usually wins: filtered air, no permanent cold opening, and the fan and interlock already exist. The licensed gasfitter confirms the burner type and the pathway.
DECISION 06Make-up air is the other half of the system
Every litre the hoods remove has to come back in. AS 1668.2-2012 Clause 3.8.3 requires make-up air to be supplied directly when the outdoor air already reaching the kitchen cannot offset the hood exhaust, and Clause 3.8.5 requires the supply fan to run whenever the exhaust runs. In an open-plan hall with no existing supply, that means a dedicated fan.
- How much. The Standard sets no percentage. In an open plan we supply about 90 % of the exhaust so the shortfall does not whistle through doors. In the worked example that is 1620 L/s against 1800 L/s.
- The balance. The remaining 180 L/s, plus about 60 L/s of flue gas leaving through the oven flues (AS/NZS 5601.1 Table G.9, 0.1 L/s per MJ/h), enters through doors and openings. Clause 3.8.4 caps the pressure drop at 12 Pa; at a 5 Pa design target that needs about 0.14 m² of free opening.
- Where. Diffusers on the far side of the hall, blowing down at low velocity. A supply grille aimed at the front of a canopy, such as one left over from a previous fit-out, pushes the plume out of the hood.
DECISION 07Check every number before it is priced
A calculation note that two contractors price differently is not finished. On a recent job every duty went into one design data file that the report, drawings and schedules quote, and every number was re-derived by a separate script written without the design engine: Colebrook friction, fitting losses, filter resistance, fan power, air balance, roof distances. Every value agreed within 2 %. Every clause was read in the Standard itself, and figures that come from judgement are marked as judgement.
Before the site measurements, the builder got a brief preliminary concept: the layout, the reasons, and a short list of the documents only others hold (site survey, construction drawings, appliance models, the architect's set-out, non-public manufacturer manuals, the NCC edition). It lets the job keep moving while the data comes in.
QUESTIONSWhat builders and owners ask
Does a kitchen exhaust in WA have to discharge 3 m above the roof?
Not under AS 1668.2-2012 for kitchen exhaust. Clause 3.10.3(b) applies the 3 m to Type A effluent; kitchen exhaust is Type B. Check the approving council's guideline, which may add a height.
Do electric fryers need a canopy?
Yes. Clause 3.3.1(b) treats any deep fryer as Type B regardless of rating. Electric fryers remove the gas interlock and allow a 600 mm filter clearance, but they still need a hood, a grease duct and a fan.
Can the canopy and ducts left by a previous tenant be reused?
Sometimes. A riser in the right place and in good condition is often worth keeping. A canopy longer or higher than the new line allows costs airflow for years, and an intake near the new discharges usually has to go.
Do gas rack ovens change the ventilation design?
Yes. Open flued ovens in a room need additional ventilation when gas input over room volume exceeds 0.4 MJ/h per m³, either through an opening direct to outside or a low-level mechanical supply with a gas interlock.
Scope: I design and calculate as a mechanical engineer (MIEAust NER). The licensed mechanical contractor supplies, installs, commissions and certifies the system, and the licensed gasfitter designs, installs and certifies the gas work and flues. More on the service: kitchen exhaust, ventilation and air conditioning design in Perth.